Overhead Building Services - Safety Alert

Here is a recent safety alert issued by Workplace Health and Safety QLD - Dec 2018.

Purpose:
The purpose of this health and safety alert is to highlight the risks of falling overhead building services caused by the failure of insert anchors. Overhead building services include air conditioning ducts, cable trays, water pipes and waste pipes.

Background:
In late 2018 two separate incidents occurred in Queensland involving insert anchors. Insert anchors are also known as post-installed anchors and use a number of installation methods including the use of a hammer, cordless drill/driver or torque wrench.
In the first incident, a large air conditioning duct, suspended from the underside of a suspended concrete slab, dropped to the floor below. The anchors were loaded in direct tension (pull out) and failed. In this incident cheap 'hammer in' type insert anchors were used. The anchor manufacturer clearly states that the anchors were unsuitable for an overhead application.
In the second incident, a 70 metre long cable tray holding heavy electric cable pulled away from a concrete wall and injured workers next to the cable tray. The cable tray was supported by a combination of threaded rods from above and cantilevered brackets that were fixed to the wall using screw bolt type insert anchors.

Contributing factors:
The incidents are being investigated. The failure of insert anchors can be caused by a number of factors including:
- overloading of the anchors failure to install the anchor in accordance with the manufacturer's instructions
- using the incorrect type1 of anchors for applications where anchor failure can cause loss of life or injury using an anchor where the manufacturer's instructions are impractical to meet (e.g. reinforcement steel in the concrete makes it impractical to drill holes of the correct diameter and depth).

Note1: Most of the larger manufacturers of post-installed anchors produce a range of anchors of differing quality for a broad range of applications. Many of the cheaper and smaller anchors are not intended for applications where the failure of the anchor can cause death or injury. Wherever the manufacturer states that certain applications are unacceptable, these instructions must be complied with.

Action required:
To reduce the likelihood of failure of insert anchors used to support overhead services ensure:
Only anchors specified as suitable for the application, with a manufacturer's load rating equal to or exceeding the maximum applied loads, are used. Insert anchors are installed in accordance with the manufacturer's instructions. Anchors are not installed in holes that are oversized, too shallow or where the concrete is cracked or damaged. A documented system that verifies the actual loading applied to the anchors is less than or equal to the maximum allowable specified by the anchor manufacturer is provided. This will usually require a professional engineer to undertake calculations and provide a certification statement.

File downloads

Related link


Need Safety Products or Uniforms »

« ISO 45001:2018

Testimonials

An excellent service

"Everything OHS provided an excellent service in the provision of our tailored OHS Manual. The manual was comprehensive and fully suited our business need with only minimal edits.

Very prompt service with the full manual received within 48 hours!"

Satisfied Clients

Landscaping and Clearing
JB Structural Landscape

JB Structural Landscape is a local business operating in Coffs Harbour and the surrounding areas.
Services include; Stone Masonry, Block Walls, Retaining Walls, Paving, Concreting and Garden Design.

JB Structural Landscape

more clients